商鋪名稱:廈門紀揚科技有限公司
聯系人:葉經理(小姐)
聯系手機:
固定電話:
企業郵箱:1094469569@qq.com
聯系地址:廈門市翔安區鼓巖路1號華論國際1003
郵編:361001
聯系我時,請說是在線纜網上看到的,謝謝!
主營:世界知名品牌的PLC 、DCS 系統備件 模塊
①Allen-Bradley(美國AB)系列產品》
②Schneider(施耐德電氣)系列產品》
③General electric(通用電氣)系列產品》
④Westinghouse(美國西屋)系列產品》
⑤SIEMENS(西門子系列產品)》
⑥銷售ABB Robots. FANUC Robots、YASKAWA Robots、KUKA Robots、Mitsubishi Robots、OTC Robots、Panasonic Robots、MOTOMAN Robots。
⑦estinghouse(西屋): OVATION系統、WDPF系統、MAX1000系統備件。
⑧Invensys Foxboro(?怂共_):I/A Series系統,FBM(現場輸入/輸出模塊)順序控制、梯形 邏輯控制、事故追憶處理、數模轉換、輸入/輸出信號處理、數據通信及處理等。Invensys Triconex: 冗余容錯控制系統、基于三重模件冗余(TMR)結構的zui現代化的容錯控制器。
⑨Siemens(西門子):Siemens MOORE, Siemens Simatic C1,Siemens數控系統等。
⑩Bosch Rexroth(博世力士樂):Indramat,I/O模塊,PLC控制器,驅動模塊等。
◆Motorola(摩托羅拉):MVME 162、MVME 167、MVME1772、MVME177等系列。
Emerson Rosemount 0065N30J0150N0350A2IMXAX8QGBR6
5 1/4
(133)
7
(177.8
11/16
(17.4)
3/4
(44.4) 25/32
(19.8)
1/4
TYP
(6.35)
390
TYP
KNOCKOUTS
FOR
1 1/16
(27)
1 3/16
(30.2)
14 ? FIREYE PRIMELINE PRODUCTS
YB110/YB230 FIREYE BURNERLOGIX? CONTROL Bulletin BL-1001
The Fireye® BurnerLogix? System is a microprocessor based burner management
control system designed to provide the proper burner sequencing, ignition and flame
monitoring protection on automatically ignited oil, gas, and combination fuel burners.
In conjunction with limit and operating controls, it programs the burner/blower motor,
ignition and fuel valves to provide for proper and safe burner operation. Through
SMART LED’S, the control provides current operating status and lockout information
in the event of a safety shutdown. Optional VFD and LCD displays are available that
may be either plugged in or mounted remotely to give full language descriptors of current status and diagnostic lockout information.
A complete BurnerLogix system includes the YB110 (YB230) chassis equipped with
the type of flame amplifier required for the application, appropriate flame detector,
plug-in programmer module, wiring base and optional alpha-numeric display. Interchangeable programmer modules allow for complete versatility in selection of function, timing and flame failure response times.
The optional alpha-numeric display is made up of 2 lines by 16 characters per line and is available in either vacuum fluorescent or liquid crystal formats. Both displays contain a fully functional keypad allowing the user to easily scroll through the various menus to view the current operating status, review programmer configuration, and lockout history. An advantage of the
BurnerLogix control family is the ability to set many of the operating parameters associated with proper and reliable burner
operation allowing inventory of various programmer types to be kept to a minimum.
Interchangeable YP programmer modules allow for complete versatility in selection of control function, timing, and flame
scanning means. Functions such as pre-purge time, recycling or non-recycling interlocks, high fire proving interlock and trial
for ignition timing of the pilot and main flame are determined by the programmer module. The BurnerLogix system can be
used with ultra-violet, auto-check infrared, flame rod, self-check ultra-violet flame scanners or direct coupled integrated scanners by choosing the proper chassis/flame amplifier module.
Wiring bases for the BurnerLogix control are available pre-wired with 4 foot lead wires color coded and marked for easy installation or with an integral terminal block capable of a accepting up to 2 X 14 AWG wires. The wiring base terminal block is available with knockouts for conduit or open ended for cabinet mounting. The pigtail wiring base is 4" X 5" and the terminal block
wiring base is 4" X 7".
Additional functions of the BurnerLogix system include:
? A consistent flame signal read-out via display module or 4-20 mA output.
? Read-out of main fuel operational hours and complete cycles via display module.
? Modbus communications via RS485 multi-drop link.
? Proof of fuel valve closure during off cycle.
? Burn-in time of program parameters occurs after 8 hours of main valve on time.
? A run/check switch which allows the operator to stop the program sequence in any of four
different positions (Purge, PTFI, MTFI or Auto).
? Remote Display mounting with NEMA 4 protection.
? Remote Reset.
? Revert to pilot can increase burner turn down.
BurnerLogix Chassis/Flame Amplifier Module
PART NUMBER DESCRIPTION
YB110UV 120 VAC input with UV non self-check amplifier
YB110UVSC 120 VAC input with UV self-check amplifier
FIREYE PRIMELINE PRODUCTS ? 15
BurnerLogix Programmer Modules
BurnerLogix Displays
BurnerLogix Wiring Bases
BurnerLogix Accessories
YB110IR 120 VAC input with IR auto-check amplifier
YB110IR2 120 VAC input with IR auto-check amplifier (special application only -consult factory)
YB110FR 120 VAC input with flame rectification amplifier
YB110DC 120 VAC input with direct coupled amplifier for use with 85UVF4-1QDWR or InSight scanner (with 59-
497-020WR cable)
YB230UV 230 VAC input with UV non self-check amplifier